Multi-Spectral Flame Detection: UV & IR flame detector uses ultraviolet and triple infrared sensors to detect hydrocarbon and non-hydrocarbon fires with high accuracy.
SIL2 Certified Design: SIL2 certified flame detector compliant with EN IEC 61508, ensuring reliable functional safety for critical industrial applications.
High-Speed Detection: UV & IR detector provides flame detection typically within 3 seconds for rapid fire response.
Advanced False Alarm Immunity: IR flame detector is immune to false triggers from sunlight, hot surfaces, welding arcs, and electrical noise.
Wide Area Coverage: UV flame detector offers a 110° ±10° field of view for efficient monitoring of large hazardous zones.
Configurable Sensitivity: UV & IR flame detector features selectable high, medium, and low sensitivity to prevent zone crossover detection. Self-Diagnostic Monitoring: Built-in automatic self-test continuously checks sensor and system health.
Explosion-Proof Construction: Flame detector housed in SS-316 stainless steel, certified for use in hazardous and explosive atmospheres.
Multiple Output Interfaces: Supports 4-20 mA analog output, relay outputs, and optional RS-485 Modbus RTU and HART communication.
Harsh Environment Protection: UV & IR detector rated IP66 and IP68 for reliable operation in extreme industrial conditions.
Technical Specifications:
Model: FLD-3311-FLP (Phoenix Series)
Detection Technology: UV (185-260 nm) & IR (3000-5000 nm)
Detection Range (Typical): – n-Heptane: up to 27 m – Kerosene / Diesel / Gasoline: up to 25 m – Methanol: up to 20 m